3C Flat Submersible Cable for Pump Motor
Certified by: BIS
| Conductor | Insulation Thickness (mm) |
Sheath Thickness (mm) |
Max Overall Dimensions (W X H) (mm) |
Max Conductor Resistance @20°C Ω/Km |
Current Carrying Capacity @40°C Amps |
||
|---|---|---|---|---|---|---|---|
| Area (Sqmm) |
No of Strands |
Max diameter of strands |
|||||
| 1.5 | 30 | 0.26 | 0.6 | 0.9 | 10.7 x 5.3 | 13.3 | 14 |
| 2.5 | 50 | 0.26 | 0.7 | 1 | 13.0 x 6.2 | 7.98 | 19 |
| 4 | 56 | 0.31 | 0.8 | 1 | 15.3 x 7.1 | 4.95 | 26 |
| 6 | 80 ± 4 | 0.31 | 0.8 | 1.1 | 19.2 x 8.4 | 3.3 | 30 |
| 10 | 80 ± 4 | 0.41 | 1 | 1.4 | 24.2 x 10.4 | 1.91 | 39 |
| 16 | 126 ± 8 | 0.41 | 1 | 1.4 | 29.0 x 12.4 | 1.21 | 55 |
Note: No. of strands and Dia of strands will be such as to meet the C.R. Value only
Note:: HP vs Current: The full load for submersible pump motors, 3 phase, 50 cycle, 415-425V
| HP | 5 | 7.5 | 10 | 12.5 | 15.5 | 17.5 | 20 | 25 | 30 | 35 |
| Amp | 7.5 | 11 | 14.9 | 18.9 | 22.5 | 25.2 | 28.4 | 35.6 | 42.3 | 50.4 |
| HP | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
| Amp | 58.1 | 62.1 | 67.5 | 73.8 | 81 | 87.3 | 93.6 | 100.8 | 108 |
Derating Factors:
For varying ambient temperatures, multiply the cable’s current carrying capacity by the corresponding factors listed below.
| Ambient Temperature (°C) | 30 | 35 | 40 | 45 | 50 |
| Rating Factor | 1.09 | 1.04 | 1 | 0.95 | 0.88 |