Features
Instrumentation cables are designed for the transmission of Analog and Digital Signals in Control Systems. Cables are designed and made to ensure an extremely high level of accuracy and sensitivity, with minimal electromagnetic noise, interference and cross-talk.
Individual pairs are colour coded for simple identification & hook-up. Individual pair shielding options are recommended for use in Intrinsically Safe Systems.
Characteristics
- Signal protection between pairs
- Electromagnetic protection from external interference
- Aluminium Mylar Tape screening protects the signal/data transmission from electromagnetic interference
- Flame & Fire Retardant options are designed to withstand extreme fire conditions, with minimal emission of toxic smoke and gases
- Solid or stranded conductors provided based on flexibility requirement of customer
Applications
- Transmission of analog & digital signals in control systems
- Audio, intercom, control, energy measurements, alarm circuits, DCS, SCADA etc.
- Primarily for indoor & dry locations
Cable Categories
- G-Type Unarmoured - Collective Screen, Sheathed Cable
- G-Type Armoured - Collective Screen, Inner Sheath, Armour, Sheathed Cable
- F-Type Unarmoured - Individual Screen, Collective Screen, Sheathed Cable
- F-Type Armoured - Individual Screen, Collective Screen, Inner Sheath, Armour, Sheathed Cable
Conductor Construction
| Nominal Area of Conductor | No. of wires / Dia of wires | ||
|---|---|---|---|
| Solid (Class 1) | Solid (Class 1) | Solid (Class 1) | |
| Sqmm | Nos. / mm | Nos. / mm | Nos. / mm |
| 0.5 | 1 / 0.80 | 7 / 0.30 | 16 / 0.20 |
| 0.75 | 1 / 0.98 | 7 / 0.37 | 24 / 0.20 |
| 1 | 1 / 1.13 | 7 / 0.43 | 32 / 0.20 |
| 1.5 | 1 / 1.38 | 7 / 0.52 | 30 / 0.25 |
| 2.5 | 1 / 1.78 | 7 / 0.67 | 50 / 0.25 |
Cable Construction
| Process | Features / Material |
|---|---|
| Conductor | Electrolytic grade Annealed Bare or Tin plated Copper Wires |
| Insulation | PVC / FRLS-PVC / HR-PVC / PE / XLPE / LSZH / FEP / PTFE / EPR or as per requirement |
| Core & Pair Identification | Insulation colouring, number printing, Ring marking or a combination of the above |
| Pairing | Twisting of two cores to form a pair |
| Screen on Individual Pair (if required) | Pair screened with Aluminium Mylar Tape of 100% coverage with Tinned Copper Drain Wire |
| Laying | Pairs laid up suitably with polyester binder tape if required |
| Collective | Screen Laid up cable screened with Aluminium Mylar Tape of 100% coverage with Tinned Copper Drain Wire |
| Sheath | PVC / FR-PVC / FRLS-PVC / HR-PVC / LSZH / FEP / PTFE or as per requirement |
Individual and/or Collective Braid Shielding, Pair Jacketing etc can be provided as well.
Electrical & Transmission Characteristics
| Electrical & Transmission Characteristics | Reference Standard |
|---|---|
| Conductor | Resistance IS 8130 |
| Dielectric Constant | IS 5608 Part 1 or BS 5308 Part 1 & 2 |
| Volume Resistivity | IS 5608 Part 2 or BS 5308 Part 1 & 2 |
| Mutual Capacitance | IS 5608 Part 3 or BS 5308 Part 1 & 2 |
| Characteristic Impedance | IEC 189 or BS 5308 Part 1 & 2 |
| Cross Talk / Attenuation | VDE 0815 |
| Inductance | VDE 0816 or BS 5308 Part 1 & 2 |
Fire Performance
| Property | Ref Standard | Flame Retardant (FR) | Flame Retardant Low Smoke (FRLS) | Low Smoke Zero Halogen (LSZH) |
|---|---|---|---|---|
| Oxygen Index | ASTM D 2863 / IS 10810-58 | >29% | >29% | >29% |
| Temperature Index | ASTM D 2863 / IS 10810-58 | >250°C | >250°C | >250°C |
| Smoke Density Rating | ASTM D 2843 | <60% | <20% | |
| Halogen Acid Gas Generation | IEC 60754-1 | <20% | <0.5% | |
| Flame Test | IEC 60332-1 | As per specification | ||
Fire Survival Cables can be provided in all of the above styles
Ring Marking & Ring Colours
| Unit | Ref Standard | Ring Marking | Colour of Ring Marking |
|---|---|---|---|
| 1, 5, 9 | Ring colours for unit 1 to 4 is Pink | ||
| 2, 6, 10 | Ring colours for unit 5 to 8 is Orange | ||
| 3, 7, 11 | Ring colours for unit 9 to 12 is Violet | ||
| 4, 8, 12 |