Technical Features
- Certified by Bureau of Indian Standards (BIS) as per IS 694: 2010
- Suitable for electrical power & lighting, wiring for buildings such as residential or commercial buildings, hotels, hospitals, and panel wiring
- Conductor Material: Annealed Bare Copper / Annealed Tinned Copper
- Insulation / Sheath Material: Polyvinyl chloride
- Single and Multi Core Cables
- Copper Purity of greater than 99.9% as per ASTM B 49
- Copper construction as per IS 8130: 2013 – Class 5
- Operating voltage up to 1100V
- Operating Temperature: -20°C to 70°C or 85°C
- Short Circuit Resistance up to 160°C
- High Voltage Test: withstands 3kV for 5 minutes
- Testing as per IS 5831: 1984
- We can manufacture Flame Retardant (FR), Flame Retardant with Low Smoke (FRLS), and Halogen-Free (LSZH)
Flame Retardant Properties
| Property | Ref Standard | Flame Retardant (FR) | Flame Retardant Low Smoke (FRLS) | Low Smoke Zero Halogen (LSZH) |
|---|---|---|---|---|
| Oxygen Index | ASTM D 2863 / IS 10810-58 | >29% | >29% | >30% |
| Temperature Index | ASTM D 2863 / IS 10810-58 | >250°C | >250°C | >250°C |
| Smoke Density Rating | ASTM D 2843 | <60% | <20% | |
| Halogen Acid Gas Generation | IEC 60754-1 | <20% | <0.5% | |
| Flame Test | IEC 60332-1 | As per specification | ||
- Oxygen Index indicates the minimum oxygen percentage required for the combustion of the PVC at ambient room temperature
- Temperature Index is the temperature at which combustion of the PVC occurs at normal atmospheric oxygen content of 21%
- Smoke Density Rating indicates the reduction in light transmission caused by the smoke generated during the burning of the PVC
- Acid Gas Generation indicates the amount of hydrochloric acid produced during the burning of the PVC
Single Core Cable
Copper Conductor & PVC Insulation – 1100V
| No. of Cores x Nominal Cross Sectional Area of Conductor | Max DC Conductor Resistance at 20°C | Nominal Insulation Thickness | Max Overall Diameter of Cable | Current Rating | |
|---|---|---|---|---|---|
| mm2 | Bare (Ω/km) | Tinned (Ω/km) | mm | mm | Amps |
| 1C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 2.6 | 4 |
| 1C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 2.6 | 4 |
| 1C x 0.75 sqmm | 26.0 | 26.7 | 0.6 | 2.8 | 8 |
| 1C x 1 sqmm | 19.5 | 20.0 | 0.6 | 3.0 | 12 |
| 1C x 1.5 sqmm | 13.3 | 13.7 | 0.7 | 3.4 | 16 |
| 1C x 2.5 sqmm | 7.98 | 8.21 | 0.8 | 4.1 | 22 |
| 1C x 4 sqmm | 4.95 | 5.09 | 0.8 | 4.8 | 29 |
| 1C x 6 sqmm | 3.30 | 3.39 | 0.8 | 5.3 | 37 |
| 1C x 10 sqmm | 1.91 | 1.95 | 1.0 | 7.0 | 51 |
| 1C x 16 sqmm | 1.21 | 1.24 | 1.0 | 8.1 | 68 |
| 1C x 25 sqmm | 0.780 | 0.795 | 1.2 | 10.2 | 86 |
| 1C x 35 sqmm | 0.554 | 0.565 | 1.2 | 11.7 | 110 |
| 1C x 50 sqmm | 0.386 | 0.393 | 1.4 | 13.9 | 145 |
| 1C x 70 sqmm | 0.272 | 0.277 | 1.4 | 16.0 | 230 |
| 1C x 95 sqmm | 0.206 | 0.210 | 1.6 | 18.2 | 280 |
| 1C x 120 sqmm | 0.161 | 0.164 | 1.6 | 20.2 | 320 |
| 1C x 150 sqmm | 0.129 | 0.132 | 1.8 | 22.5 | 375 |
| 1C x 185 sqmm | 0.106 | 0.108 | 2.0 | 24.9 | 440 |
| 1C x 240 sqmm | 0.0801 | 0.0817 | 2.2 | 28.4 | 530 |
| 1C x 300 sqmm | 0.0641 | 0.0654 | 2.4 | 31.0 | 620 |
| 1C x 400 sqmm | 0.0486 | 0.0495 | 2.6 | 33.2 | 740 |
| 1C x 500 sqmm | 0.0384 | 0.0391 | 2.8 | 37.5 | 790 |
| 1C x 630 sqmm | 0.0287 | 0.0292 | 3.0 | 42.0 | 880 |
Single Core Cable
Copper Conductor, PVC Insulation & PVC Sheath – 1100V
| No. of Cores x Nominal Cross Sectional Area of Conductor | Max DC Conductor Resistance at 20°C | Nominal Insulation Thickness | Nominal Sheath Thickness | Max Overall Diameter of Cable | Current Rating | |
|---|---|---|---|---|---|---|
| mm2 | Bare (Ω/km) | Tinned (Ω/km) | mm | mm | mm | Amps |
| 1C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 0.9 | 4.3 | 4 |
| 1C x 0.75 sqmm | 26.0 | 26.7 | 0.6 | 0.9 | 4.5 | 8 |
| 1C x 1 sqmm | 19.5 | 20.0 | 0.6 | 0.9 | 4.7 | 12 |
| 1C x 1.5 sqmm | 13.3 | 13.7 | 0.6 | 0.9 | 5.4 | 16 |
| 1C x 2.5 sqmm | 7.98 | 8.21 | 0.7 | 1.0 | 6.2 | 22 |
| 1C x 4 sqmm | 4.95 | 5.09 | 0.8 | 1.0 | 6.8 | 29 |
| 1C x 6 sqmm | 3.30 | 3.39 | 0.8 | 1.1 | 7.5 | 37 |
| 1C x 10 sqmm | 1.91 | 1.95 | 1.0 | 1.3 | 9.4 | 51 |
| 1C x 16 sqmm | 1.21 | 1.24 | 1.0 | 1.4 | 10.9 | 68 |
| 1C x 25 sqmm | 0.780 | 0.795 | 1.2 | 1.4 | 13.6 | 86 |
| 1C x 35 sqmm | 0.554 | 0.565 | 1.2 | 1.6 | 15.5 | 110 |
| 1C x 50 sqmm | 0.386 | 0.393 | 1.4 | 2.0 | 18.1 | 145 |
| 1C x 70 sqmm | 0.272 | 0.277 | 1.4 | 2.2 | 20.8 | 230 |
| 1C x 95 sqmm | 0.206 | 0.210 | 1.6 | 2.4 | 23.6 | 280 |
| 1C x 120 sqmm | 0.161 | 0.164 | 1.6 | 2.5 | 26.0 | 320 |
Two Core Cable
Copper Conductor, PVC Insulation & PVC Sheath – 1100V
| No. of Cores x Nominal Cross Sectional Area of Conductor | Max DC Conductor Resistance at 20°C | Nominal Insulation Thickness | Nominal Sheath Thickness | Max Overall Diameter of Cable | Current Rating | |
|---|---|---|---|---|---|---|
| mm2 | Bare (Ω/km) | Tinned (Ω/km) | mm | mm | mm | Amps |
| 2C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 0.9 | 6.9 | 4 |
| 2C x 0.75 sqmm | 26.0 | 26.7 | 0.6 | 0.9 | 7.3 | 8 |
| 2C x 1 sqmm | 19.5 | 20.0 | 0.6 | 0.9 | 7.6 | 12 |
| 2C x 1.5 sqmm | 13.3 | 13.7 | 0.6 | 0.9 | 8.9 | 16 |
| 2C x 2.5 sqmm | 7.98 | 8.21 | 0.7 | 1.0 | 10.3 | 22 |
| 2C x 4 sqmm | 4.95 | 5.09 | 0.8 | 1.0 | 11.6 | 29 |
| 2C x 6 sqmm | 3.30 | 3.39 | 0.8 | 1.1 | 13.0 | 37 |
| 2C x 10 sqmm | 1.91 | 1.95 | 1.0 | 1.3 | 16.5 | 51 |
| 2C x 16 sqmm | 1.21 | 1.24 | 1.0 | 1.4 | 19.4 | 68 |
| 2C x 25 sqmm | 0.780 | 0.795 | 1.2 | 1.4 | 23.8 | 86 |
| 2C x 35 sqmm | 0.554 | 0.565 | 1.2 | 1.6 | 27.2 | 110 |
| 2C x 50 sqmm | 0.386 | 0.393 | 1.4 | 2.0 | 32.0 | 145 |
| 2C x 70 sqmm | 0.272 | 0.277 | 1.4 | 2.2 | 36.8 | 230 |
| 2C x 95 sqmm | 0.206 | 0.210 | 1.6 | 2.4 | 41.8 | 280 |
| 2C x 120 sqmm | 0.161 | 0.164 | 1.6 | 2.5 | 46.2 | 320 |
Three Core Cable
Copper Conductor, PVC Insulation & PVC Sheath – 1100V
| No. of Cores x Nominal Cross Sectional Area of Conductor | Max DC Conductor Resistance at 20°C | Nominal Insulation Thickness | Nominal Sheath Thickness | Max Overall Diameter of Cable | Current Rating | |
|---|---|---|---|---|---|---|
| mm2 | Bare (Ω/km) | Tinned (Ω/km) | mm | mm | mm | Amps |
| 3C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 0.9 | 7.3 | 4 |
| 3C x 0.75 sqmm | 26.0 | 26.7 | 0.6 | 0.9 | 7.7 | 8 |
| 3C x 1 sqmm | 19.5 | 20.0 | 0.6 | 0.9 | 8.1 | 12 |
| 3C x 1.5 sqmm | 13.3 | 13.7 | 0.6 | 0.9 | 9.4 | 16 |
| 3C x 2.5 sqmm | 7.98 | 8.21 | 0.7 | 1.0 | 10.9 | 22 |
| 3C x 4 sqmm | 4.95 | 5.09 | 0.8 | 1.0 | 12.4 | 29 |
| 3C x 6 sqmm | 3.30 | 3.39 | 0.8 | 1.2 | 13.8 | 37 |
| 3C x 10 sqmm | 1.91 | 1.95 | 1.0 | 1.4 | 17.7 | 51 |
| 3C x 16 sqmm | 1.21 | 1.24 | 1.0 | 1.4 | 20.6 | 68 |
| 3C x 25 sqmm | 0.780 | 0.795 | 1.2 | 1.5 | 25.6 | 86 |
| 3C x 35 sqmm | 0.554 | 0.565 | 1.2 | 1.6 | 29.3 | 110 |
| 3C x 50 sqmm | 0.386 | 0.393 | 1.4 | 2.0 | 34.6 | 145 |
Four Core Cable
Copper Conductor, PVC Insulation & PVC Sheath – 1100V
| No. of Cores x Nominal Cross Sectional Area of Conductor | Max DC Conductor Resistance at 20°C | Nominal Insulation Thickness | Nominal Sheath Thickness | Max Overall Diameter of Cable | Current Rating | |
|---|---|---|---|---|---|---|
| mm2 | Bare (Ω/km) | Tinned (Ω/km) | mm | mm | mm | Amps |
| 4C x 0.5 sqmm | 39.0 | 40.1 | 0.6 | 0.9 | 8.0 | 4 |
| 4C x 0.75 sqmm | 26.0 | 26.7 | 0.6 | 0.9 | 8.4 | 8 |
| 4C x 1 sqmm | 19.5 | 20.0 | 0.6 | 0.9 | 8.8 | 12 |
| 4C x 1.5 sqmm | 13.3 | 13.7 | 0.6 | 1.0 | 10.4 | 16 |
| 4C x 2.5 sqmm | 7.98 | 8.21 | 0.7 | 1.0 | 12.0 | 22 |
| 4C x 4 sqmm | 4.95 | 5.09 | 0.8 | 1.0 | 13.6 | 29 |
| 4C x 6 sqmm | 3.30 | 3.39 | 0.8 | 1.2 | 15.5 | 37 |
| 4C x 10 sqmm | 1.91 | 1.95 | 1.0 | 1.4 | 19.5 | 51 |
| 4C x 16 sqmm | 1.21 | 1.24 | 1.0 | 1.4 | 23.0 | 68 |
| 4C x 25 sqmm | 0.780 | 0.795 | 1.2 | 1.6 | 28.5 | 86 |
| 4C x 35 sqmm | 0.554 | 0.565 | 1.2 | 1.7 | 32.7 | 110 |
| 4C x 50 sqmm | 0.386 | 0.393 | 1.4 | 2.0 | 38.6 | 145 |
Please refer to IS 3961 for Derating factors for the Current Rating.